← All posts

Acoustic enclosures for two R290 refrigeration units in pharmaceutical process cooling

Two identical stainless steel acoustic enclosures with roof air outlets and pipe connections on an industrial site

Starting point

For two refrigeration units using the refrigerant R290 for process cooling in a pharmaceutical production plant, two acoustic enclosures were built entirely from INOX (stainless steel).

Project goal and measured result

The goal was to reduce the total noise emissions of the refrigeration units by 14 dB(A). The result speaks for itself – or rather: it is considerably quieter. Based on in-situ measurements, a noise reduction of 15.6 dB(A) was achieved, exceeding the project goal.

−14 dB(A)Project goal for total noise emissions
−15.6 dB(A)achieved, verified by in-situ measurements
86,000 m³/hair volume per unit at an air velocity of 5 m/s

Key technical facts

  • Refrigerant: R290 (propane) – a natural, energy-efficient refrigerant with a very low GWP.
  • Safety concept: Integrated ATEX ventilation for safe operation with a flammable refrigerant.
  • Air flow: Designed for an air volume of 86,000 m³/h per unit to ensure reliable heat rejection at an air velocity of 5 m/s.
  • System design: Two identical acoustic enclosures provide a uniform, easy-to-maintain solution for two separate units.

Integrated engineering approach

Acoustics and plant engineering must be planned together – from air flow and ATEX safety to the required sound insulation.

Originally published in German on silent-mode.com

Request a project

Send us the unit type, quantity and location – or get a budget price straight from the configurator.

Silent Engineering di Romolo Vicari
ForCoTech · Silent-Mode
Via Trento 22 · 23875 Osnago (LC) · Italy
E-Mail: info@forcotech.com