Attachment silencer of perforated HSA3 tubes Ø 200 mm for heat pumps, chillers and dry coolers with upward discharge: reduces fan noise in the exhaust path with a pressure drop of only about 8 Pa – fibre-free, non-combustible (A1) and suitable for outdoor use without additional weather protection.
✓ Calculated locally in your browser✓ no cookies, no tracking✓ data only leaves your browser when you request a quotation
New – pre-design. The insertion loss values are estimates based on the HSA3 measurements; the test to DIN EN ISO 7235 on the prototype is in preparation. Pressure drop and module sizing are calculated.
Air flow and available external pressure are given in the unit data sheet (fan data). With several units, each unit gets its own silencer.
Settling length so that all tubes receive an even flow – guide value 500 mm, design per project.
The modules are hooked into the slot of MiniTec profiles 45 × 45 mm. Number and arrangement follow from the air flow (max. 5 m/s in the tubes) and the unit footprint. All-metal: absorbs no water, UV and frost resistant, washable, recyclable as a single material.
The silencer reduces fan noise in the exhaust path. With your own octave band values from the data sheet the A-weighted reduction becomes more accurate.
Generated from your current design – for your bill of quantities. Please check the values before tendering.
All values are guide values. The binding design (acoustics, air side, structure) is carried out per project by our engineering. An exhaust silencer only reduces fan noise in the exhaust path – for high reductions or loud compressors a full enclosure is the better solution.
Your configuration is sent along. We check the design for your project and usually reply within 2–3 working days with a quotation.
About ForCoTech: ForCoTech is the acoustic enclosure brand of Silent Engineering di Romolo Vicari (Osnago, Italy), manufactured with Absora technology. Besides full enclosures and noise barriers we supply fibre-free exhaust silencers of HSA3 tubes (non-combustible, A1) for heat pumps, chillers and dry coolers. More about us: www.forcotech.com · Contact: info@forcotech.com